VA Power Calculator
Calculate the required VA burden rating for your current transformer
Correct dimensioning of a current transformer's burden is critical for measurement accuracy. An insufficient VA rating leads to saturation and inaccurate measurements. This calculator considers cable losses, connected instrument consumption and contact resistance to recommend the optimal VA rating.
Input values
Result
- Cable burden
- 1.75 VA
- Instrument burden
- 0.50 VA
- Contact resistance
- 0.10 VA
- Total burden
- 2.35 VA
- Recommended VA rating
- 2.5 VA
Burden distribution
CableInstrumentsContact
VA rating utilization
94 %
Calculation formula
Cable resistance:
R = (2 × L × 0,0175) / ACable losses:
PKabel = Is² × RTotal burden:
Pges = PKabel + PGeräte + 0,1 VAWhere ρ = 0.0175 Ω·mm²/m is the resistivity of copper, L the one-way cable length in m and A the cable cross-section in mm². The factor 2 accounts for the forward and return conductor.